Terms and conditions
| Power Supply | 18V ~ 32V DC |
| Power Consumption | Monitoring mode: <13.5mA; Alarm mode: <14mA |
| Protection Range | Distance between beams: 14m; Distance between beam and wall: <7m |
| Alarm Threshold | 1.4dB |
| Optical Path Length | 5 to 60 meters |
| Encoding Mode | On-site electronic coding (Addressing: 1 ~ 324) |
| Operating Conditions | Indoor use; Temperature: -10°C to +55°C |
| Installation Height | 0.5 to 1 meter from the top of the building (ceiling) |
| Dimensions | 180 mm × 83 mm × 73 mm |
| Weight | 560 grams |